e-Shop

UNITRONIC® LiYY (TP)

Data transmission cable with colour code acc. to DIN 47100 and twisted pairs

UNITRONIC® LiYY (TP): Low-frequency PVC data cable DIN 47100 coded, Flexible, 0.34mm² Maxi TERMI-POINT®, Twisted Pairs, Flame retardant, Instrumentation Control

  • TP = twisted pair
  • CPR: Article number choice under www.lappkabel.com/cpr

CE Fire

Article number Number of pairs and conductor cross section (mm²) Outer diameter [mm] Copper index (kg/km) Weight (kg/km) Base Unit Price (base price)
UNITRONIC® LiYY (TP)
0035101
2 x 2 x 0.14 4.5 5.4 25.5
0035102
3 x 2 x 0.14 5 8 32
0035103
4 x 2 x 0.14 5.6 10.7 38.5
0035104
5 x 2 x 0.14 5.8 13.4 45.5
0035105
6 x 2 x 0.14 6.3 16.1 51
0035108
10 x 2 x 0.14 8.1 26.9 77.5
0035110
12 x 2 x 0.14 8.3 32.3 94.5
0035113
16 x 2 x 0.14 9.2 43 110.5
0035160
2 x 2 x 0.25 5.7 9.6 38
0035161
3 x 2 x 0.25 6.3 14.4 48
0035162
4 x 2 x 0.25 7 19.2 59
0035163
6 x 2 x 0.25 7.9 28.8 80
0035164
8 x 2 x 0.25 9.3 38.4 98
0035170
2 x 2 x 0.5 7.3 19.2 72
0035171
3 x 2 x 0.5 8.1 28.8 83
0035172
4 x 2 x 0.5 8.8 38.4 115
0035174
8 x 2 x 0.5 12.3 76.8 206
0035175
10 x 2 x 0.5 13.3 96 247
Available from stock
Available soon
Not available

Benefits

  • Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects)

Application range

  • Dry or damp rooms

Product features

  • Twisted in pairs to reduce decoupling. As a result, additional screening is often not required.
  • Flame-retardant according IEC 60332-1-2

Norm references / Approvals

  • Based on VDE 0812

Product Make-up

  • Fine-wire strand made of bare copper wires
  • Core insulation made of PVC
  • TP structure
  • Outer sheath made of PVC
    Outer sheath colour: grey (similar to pebble grey/ RAL 7032)

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000104
  • ETIM 5.0 Class-Description: Control cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000104
  • ETIM 6.0 Class-Description: Control cable

Core identification code

  • DIN 47100, refer to Appendix T9

Mutual capacitance

  • Approx. 120 nF/km

Inductivity

  • approx. 0.65 mH/km

Conductor stranding

  • Fine copper wire strands

Minimum bending radius

  • Occasional flexing: 10 x outer diameter
  • Fixed installation: 4 x Outer diameter

Temperature range

  • Occasional flexing: -5°C to +70°C
  • Fixed installation: -40°C to +80°C

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related surcharges.
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum
  • Please specify the preferred type of packaging (e.g. 1 x 500 m drum or 5 x 100 m coils).
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.
  • Prices are net prices without VAT and surcharges. Sale to business customers only.